Water Leak Detection System (WLDS)

System Overview

The AGNI Water Leak Detection System (WLDS) is a specialized monitoring and alarm system designed to detect the presence of water or conductive liquids at an early stage preventing costly damage to sensitive areas such as data centers, electrical switch rooms, server racks, raised floors, laboratories, and other application-critical facilities.
The system provides continuous real-time monitoring and issues an immediate alert when water leak is  detected, allowing maintenance personnel to respond before a major leak or flooding occurs.

Operating Principle

The WLDS operates using sensing cables or probes that continuously monitor for moisture or conductive liquids along their length or at specific points.
When water or another conductive liquid comes into contact with the sensor, it changes the electrical characteristics (resistance or capacitance) of the sensing element. 

The Leak Detection Controller interprets this change and:

Provision BMS integration card Sends a signal to the Building Management System (BMS) or Other ALarm Control Panel For integration and remove monitoring.

System Types

There are two primary types of water leak detection systems:

Zone (Non-Addressable) Type

Addressable (Distance-Readable) Type

System Component & Description

Component

Description

Leak Detection Control System

WLD Detection System that monitors sensor cables or prabes, dispalys leak and fault conditions, and interfaces with BMS or alarm systems.

Water Leak Sensing Cable 

Polymer-coated, multi-core cable that detects conductive liquids along its entire length resettable after drying.

Spot Sensors / Point Probes

Fixed-point detectors for localized leak monitoring (e.g., under HVAC units or valves).

End-of-Line

Installed at the end of sensing cables to complete the circuit and enable supervision.

Interface Module / Relay Output Card

Provides potential-free contacts for alarm and fault output to external systems (BMS, fire alarm, etc.).

Power Supply / Battery Backup

Ensures continuous operation during power outages; typically 24V DC. Battery Charging Capabilities 7.2ah 12v x 2 nos

Mounting Accessories

Clips, color cable ties, junction boxes, and cable management hardware for proper instalation.

Technical Features

Environmental and Electrical Specifications

Parameter

Typical Specification

Detection Method

Conductive sensing (resistance change)

Sensing Cable Length

Depending on the requirements

Leak Location Accuracy 

±1.5 meter addressable type 

Alarm Response Time

< 10 seconds

Operating Voltage

24V DC nominal

Operating Temperature

0°C to 55°C 

Communication Protocols

Modbus RTU / BACnet / RS-485

Alarm Outputs

Relay contacts (NO/NC), 1A @ 30V DC 

Enclosure Rating

IP30 (controller), IP65 (sensor junction boxes)

Compliance 

CE, RoHS, UL, IEC 61010-1

Advantages

Typical Applications

Standards and Compliance

The Water Leak Detection System and its components typically conform to:

01.

UL 61010-1

Safety requirements for electrical equipment

02.

IEC 60364

Low-voltage electrical installations

03.

EN 61326

EMC requirements for electrical equipment

04.

CE and RoHS compliance

05.

BS 8489-1

Protection of electrical installations

05.

NFPA 75

Protection of IT and electronic equipment rooms