Agni CPWD DSR Fire Alarm Panel with PA System and Talk Back
The Agni 6 and 10 Zone Fire Alarm Panel is a microprocessor-based conventional fire alarm panel built as per CPWD DSR specifications. Fire detection, zone-wise public address and a 23-line simplex talk-back system sit in one double-door cabinet, with two amplifiers (main and standby) and space for two 12V 65Ah batteries.
Conventional fire alarm panel as per CPWD DSR
Government and institutional tenders often ask for a fire panel as per CPWD DSR: a zonal fire panel, a public address system and a talk-back link, working as one system. The AGNI DSR conventional fire alarm system supplies all three in a single factory-built rack, so contractors get one product to submit, install and test. Agni Instruments Engineers India Pvt. Ltd. has manufactured fire detection equipment in Okhla, New Delhi since 1989, and this panel carries that years of experience.
The AGNI 6 and 10 Zone Fire Alarm Panel is a microprocessor-based conventional fire alarm control panel built as per CPWD DSR specifications, with a PA system and talk back in the same cabinet. If you are looking to CPWD DSR fire alarm panel for a government tender, a hospital, an institution or an industrial site, this system gives you detection, zone-wise public address and a talk-back link as one factory-assembled unit.
Agni Instruments Engineers India Pvt. Ltd. is a fire alarm panel manufacturer in India, Since 1989. As a DSR fire alarm system manufacturer, we build the panel, the amplifiers and the PA control desk ourselves. You deal with one supplier for the whole CPWD fire alarm system, which makes tender compliance and after-sales support simpler.
The 6 zone and 10 zone fire alarm panels share the same structure. The only differences are the number of detection zones and the amplifier wattage. The 6 zone DSR panel uses 100 W amplifiers and the 10 zone DSR panel uses 250 W amplifiers. The cabinet, talk-back, battery space and other technical parameters are identical. Zone expansion is available up to 36 zones, so the system can grow with the building.
The control panel is driven by a Cortex-M0 processor. It has a high-resolution 16x2 LCD for event information and a 12-key matrix keypad for operation. Colour LEDs show power, battery, silence, fire, open circuit, short circuit, healthy, enable and disable. Every zone can be programmed through the keypad, and each zone has its own sounder enable or disable control and programmable voltage isolation. The panel stores up to 999 events with a real-time clock. The zone-wise walk test lets engineers test smoke, heat and manual devices during commissioning without shutting down the rest of the system. Every zone also has reverse voltage protection, and the panel is protected against high mains voltage between 230V and 350V AC.
The announcement control desk has a 12-1 all-call matrix keypad with a seven-segment display, so operators can speak to selected zones or to the whole building. A handheld gooseneck microphone with an on/off switch and cardioid pickup is included, along with audio monitoring and volume controls. Two amplifiers are supplied in every panel, and a changeover switch moves between the main and the standby unit, so announcements continue if one amplifier fails.
The 23-line simplex talk-back system gives the fire control room a voice link to the field. It works as press-to-talk, half-duplex communication with TALK and LISTEN operation and the "OVER" protocol, which keeps emergency messages clear between the control room and the building. This is why many buyers choose a 10 zone fire alarm panel with talk back for hospitals, campuses and large commercial complexes.
The AGNI DSR conventional fire alarm system follows EN 54-2 for control and indicating equipment and EN 54-4 for power supply equipment. The complete system is designed to conform to IS 2189:2008. It is manufactured under an ISO 9001 quality management system, and the panel is CE conformant under the Low Voltage Directive 2014/35/EU. Together, these make it a dependable choice if you need a CPWD fire alarm panel with PA and talk back for a project that follows the DSR specification.
Certifications & Compliance
CEÂ
European Conformity
EN54-4 | EN45-2
European Certification
UL 217:2024
Functionality Compliance
IS 2189: 2022
NABL Laboratories Test Certified
ERTL North (Govt. India)
Functional Test Certified
Standard Code of PracticeÂ
INDIA- BIS | NBC
Approved Department
Government of IndiaÂ
Department of CPWD / PWD
Complied with CPWD DSR
Our fire safety engineers respond within 2 hours with competitive pricing for your project
Call: 9811522993 / 9811554440
6 Zone and 10 Zone: what changes
Only the detection zone count and the amplifier wattage differ. All other technical parameters, including the cabinet size, are the same. Pick the 6 Zone panel and the 10 Zone panel where you need more announcement lines and amplifier power
|
Feature |
CPWD DSR 10 Zone (17.1.10) |
CPWD DSR 6 Zone (17.1.11) |
|---|---|---|
|
PA zone selector |
10 line |
6 line |
|
PA amplifier power |
250 W, 2 nos (main and standby) |
100 W, 2 nos (main and standby) |
|
Control panel, talk back, power supply |
Identical on both variants |
Identical on both variants |
|
Cabinet |
H 1420 × W 600 × D 425 mm |
H 1420 × W 600 × D 425 mm |
|
Battery space |
2 × 12 V 60 Ah batteries |
2 × 12 V 60 Ah batteries |
Full Technichal Specificaiton - Agni Veiga Series FACP
All specifications for the analogue addressable fire alarm system, covering general performance, power supply, inputs/ outputs, and mechanical/ compliance other parameters.
|
Parameter |
Specification |
|---|---|
|
Control Type |
Agni Veiga Micro Processor based Intelligent Addressable |
|
Part Number |
VEIGA-FAP-1001 / VEIGA-FAP-1002 / VEIGA-FAP-1004 |
|
Loops Supported |
1 / 2 / 4 Loops (Model Dependent) |
|
Devices per Loop |
Maximum 240Â |
|
Loop Length |
Maximum Loop Length: Up to 2,000 m (6,562 ft / 1.24 miles) per channel using 12 AWG (3.1 mm²) twisted-pair cable, subject to cable copper conductor resistance, joint quality, and site installation conditions. |
|
Protocol |
Agni Addressable Protocol |
|
Event Log Capacity |
4000 Events (Date & Time Stamped) |
|
Display |
Graphical LCD with Factory-Customizable Standard & Small Size Font (240–320 Characters) |
|
Keypad |
Soft Touch Keypad |
|
Zonal LEDs |
18 Zones |
|
Programmable Groups |
64 |
|
False Alarm Management |
Yes - Integrated |
|
Auto Learn Function |
Yes |
|
Network Communication |
RS-485 Veiga Network (Optional - FAP-3002 card required) |
|
Parameter |
Specification |
|---|---|
|
Mains Supply |
230 VAC ±10% / −15%, 50 Hz |
|
Internal Power Supply |
Standard system and loop device capacity Intelligent PSU |
|
Output Voltage |
19.8 – 29.7 VDC (Tolerance ±0.1%) |
|
Auxilary Supply Output |
400 mA @ 21-28 VDC |
|
Battery Charging Voltage |
27.3 VDC @ 20°C (Temperature Compensated) |
|
Charging Current |
700 mA (Current Limit. Programmable) |
|
Battery Capability |
System / Loop : 7 Ah / 12 Ah | 17 Ah | 24 Ah | 27 Ah +12v x 2=24v |
|
Battery Type |
2 × 12 V VRLA (Sealed Lead Acid) |
|
Standby Current (Quiescent) |
Approx. 220–230 mA |
|
Alarm Current |
Up to 100 mA |
|
Max Quiescent Current |
Approx. 230 mA @ 28 V |
|
Battery Standby |
Normal Standby: 24 Hours |
|
Charging Behaviour |
Charging suppressed during alarm condition |
|
Parameter |
Specification |
|---|---|
|
Sounder Circuits |
2 × 400 mA @ 21–28 VDC (28 V polarity reversal, monitored) |
|
EOL Resistor (Sounders) |
6K8 Ohm 5% 0.25 W | Monitoring current limit 28 mA, fused at 500 mA |
|
Sounder Load |
devices @ 35 mA each |
|
Common Fire Relay |
Clean C/O – Max 3 A @ 30 VDC (Unfused) |
|
Common Fault Relay |
Maintained C/O – Max 3 A @ 30 VDC (Unfused) |
|
Inputs: CC / PULSE |
Switched −ve inputs, connect to 0 V to trigger. Max input 30 VDC. Non-latching. Protected via 10K Ohm impedance, 3v6 Zener diode |
|
Earth Fault Monitoring |
Yes |
|
PBUS Output |
RS-485 / Optional Port – RSU Comms, fused at 20 mA |
|
Zone Normal Threshold |
Minimum 192 analogue value (0 – 255 range) |
|
Temp Sense Input |
Thermistor TTC5103 – 10,000 Ohms @ 25°C (battery temperature compensation) |
|
Loop (Addressable Circuit) |
Max current 500 mA | Max 240 devices per loop |
|
Detection Zones |
1 to 18 Detection Zones |
|
Parameter |
Specification |
|---|---|
|
Enclosure Material |
1.2 mm Mild Steel |
|
Protection Rating |
IP30 |
|
Finish |
Powder-Coated – Colour RAL ECRAL7035UL035L Interpon (Red/Blue Fascia Options) |
|
Front Fascia |
Soft Touch Key Pad / Standard Sticker Label – Blue or Red |
|
System Internal |
Accessibility front door locking arrangement |
|
Dimensions (1 to 2 Loop) |
350 W × 300 H × 80 D (mm) |
|
Dimensions (2 to 4 Loop) |
395 W × 465 H × 100 D (mm) |
|
Cable Entry |
Via 20 mm knockouts – Top and Rear of Cabinet |
|
Programmable Company Logo |
Yes |
|
Compliance Standard |
UL 217|2024 (functionality Compliance) |
|
BIS Standard |
IS 2189:2022 – Code of Practice / NABL Tested |
|
Certification |
EN54-4 | EN54-2Â , CE Marked (European noms &Â Conformity} |
|
Lab Tested |
ERTL North (Govt. India) |
|
Warranty |
12 Months |
|
Veiga Seires |
Part Number |
|---|---|
|
1 to 4 Loop Addressable Fire Alarm Control Panel |
VEIGA-FAP-1001 / VEIGA-FAP-1002 / VEIGA-FAP-1004 |
|
Network Active Repeater Panel |
VEIGA-FAP-2001 |
|
BACnet/ModBus Card |
FAP-ModBus |
|
RS-485 Network communication card |
VEIGA-FAP-3002 |
|
Handheld Programmer |
VEIGA-IND-ALPU1000 |
|
Addressable Photothermal(Multi) Detector |
VEIGA -IND-OH |
|
Addressable Optical Smoke Detector |
VEIGA -IND-OP |
|
Addressable ROR cum Fixed Temperature |
VEIGA -IND-HT |
|
Standard Detector Base |
IND-MB |
|
Intelligent Addressable Loop Sounder Base |
IND-S2MB / IND-SV2MB |
|
Isolator Base |
IND-ISO-B (Comming Soon) |
|
Intelligent Addressable Loop Sounder cum Beacon |
IND-WSM+LPM |
|
Intelligent Addressable Manual Call Point |
IND-ALCP100 |
|
Addressable Input/Monitor Module |
IND-VMI100 |
|
Addressable Control Module |
IND-VMIC-120 |
|
Addressable Zone Monitor Module |
IND-VMCZ100 |
|
Addressable Isolator Module |
IND-LVMX100 |
Agni DSR conventional fire alarm panel
Designed as per IS 2189:2008Â and backed by 37 years of manufacturing experience, the Agni panel combines fire protection, advanced monitoring and strong construction for fire alarm installations. The 10 Zone and 6 Zone systems share every feature below.Â
Microprocessor-based control panel
Microprocessor-based control panel
Fire control panel with 12 detection zones and a high-resolution 16×2 LCD for event infromation. Zones are expandable up to 120.
- Event LEDs for power, battery, silence, fire, open circuit, short circuit, communication, healthy, enable, disable and more
- Programmable zone voltage isolation with output voltage cut-off
- Programmable address mapping for every zone from the matrix keypad
- Event log of up to 999 records with real date and time clock
- Zone-wise sounder enable/disable control
- Zone-wise device walk test for detectors and devices, so commissioning is faster and the rest of the system stays in service
- Reverse-voltage protection on every zone for 15 seconds, protecting the connected active or passive devices
- High-voltage protection between 230 V and 350 V AC
Optional RS-485 communication port
Provision for an RS-485 port to integrate the panel with other panels.
Common protential-free relay outputs
Software-driven panel with potential-free relay outputs (C/NC/NO) for fire, open circuit and short circuit conditions. Interface easily with hooters, automatic HVAC shutdown systems or emergency controls.
Power, monitoring and enclosure
Power
Provision for an RS-485 port to integrate the panel with other panels.
Common protential-free relay outputs
Software-driven panel with potential-free relay outputs (C/NC/NO) for fire, open circuit and short circuit conditions. Interface easily with hooters, automatic HVAC shutdown systems or emergency controls.
1 to 4 Addressable Loops
Supports 1, 2, or 4 analogue addressable loops (model dependent), each carrying up to 240 device 0.936 to 1.242 miles — scalable for small sites to large multi-building installations
Graphical LCD Display
Large graphical LCD with factory customized adjustable mini font size 240 to 320cs character and soft-touch keypad for fast, intuitive navigation — simplifying both commissioning and day-to-day maintenance.
False Alarm Management
Integrated intelligent false alarm management in the device or system firmware logic that reduces unwanted activations, which is critical for hospitals, offices, and other facilities where false alarms can disrupt operations
Auto Learn Function
Auto Learn Function: Automatically scans SLC loops, identifies all connected addressable devices, and registers them with the Fire Alarm Control Panel (FACP), intelligence faster commissioning and simplified system setup.
4000-Event Log
Date and time-stamped record of 4000 system events — alarms, faults, and operator actions — stored securely in non-volatile memory for audits and fire investigations.
Loop Fault Diagnostics
Active loop fault detection and diagnostics with real-time reporting. Isolates faults to prevent a single fault from disabling an entire detection zone.
64 Programmable Groups
Up to 64 programmable cause-and-effect groups with 18 zonal LEDs — providing granular control over evacuation zones, output sequences, and alarm response logic.
RS-485 Networking
Optional RS-485 Veiga network card (FAP-3002) bridge of multi-panel networking, centralized monitoring across up to 32 nodes, and optional BACnet/Modbus IP BMS integration